Error LED2
Run LED2
Error LED1
Run LED1
Power contact
+24 V
Power contact 0 V
+Input 1
-Input 1
GND
Shield
+Input 2
-Input 2
GND
Shield
Top view
Contact assembly
EL3602 | 2-channel analog input terminal ±10 V, ±5 V, ±2.5 V, ±1.25 V, differential input, 24 bits
The EL3602 analog input terminal handles signals in the ranges ±10 V, ±5 V, ±2.5 V and ±1.25 V. The voltage is digitised to a resolution of 24 bits, and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the EtherCAT Terminal have differential inputs and possess a common, internal ground potential. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
| Technical data |
EL3602 | ES3602 |
| Number of inputs |
2 (differential) |
| Power supply |
via the E-bus |
| Technology |
differential input |
| Signal voltage |
-10…+10 V, -5…+5 V, -2.5…+2.5 V, -1.25…+1.25 V (parameterisable) |
| Oversampling factor |
– |
| Distributed clocks |
– |
| Distributed clock precision |
– |
| Internal resistance |
> 200 kΩ |
| Input filter limit frequency |
3 kHz |
| Common-mode voltage UCM |
35 V max. |
| Resolution |
24 bits (incl. sign) |
| Conversion time |
20 ms default setting, 1…400 ms configurable |
| Input signal bandwidth |
– |
| Measuring error |
< ±0.01 % at 25 °C, 50 Hz filter (relative to full scale value) |
| Electrical isolation |
500 V (E-bus/signal voltage) |
| Current consumption power contacts |
– |
| Current consumption E-bus |
typ. 190 mA |
| Crosstalk attenuation |
> 60 dB |
| Special features |
various filter times, limit value monitoring, high precision |
| Weight |
approx. 60 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all ESxxxx terminals |
| Approvals |
CE, UL, Ex |
 |
 |
| Special terminals |
|
| EL3602-0010 |
signal voltage -75…+75 mV, measuring error < ±0.05 % at 25 °C (relative to full scale value, 50 Hz filter) |
 |
 |