The EP2008 EtherCAT Box with digital outputs connects binary control signals from the controller on to the actuators at the process level. The eight outputs handle load currents of up to 0.5 A and indicate their status through light emitting diodes. The signals are optionally connected via M8 (EP2008-0001) or M12 (EP2008-0002) screw type connectors. The outputs are short-circuit-proof and protected against inverse connection.
| Technical data | EP2008-0001 | EP2008-0002 |
|---|---|---|
| Number of outputs | 8 | |
| Output connections | M8, screw type | M12, screw type |
| Protocol | EtherCAT | |
| Bus interface | 2 x M8, shielded, screw type | |
| Load type | ohmic, inductive, lamp load | |
| Nominal output voltage | 24 V DC (-15 %/+20 %) | |
| Max. output current | 0.5 A (short-circuit-proof) per channel | |
| Short circuit current | typ. 1.5 A | |
| Distributed clocks | – | |
| Auxiliary power current | typ. 20 mA + load | |
| Current consumption from US (without sensor current) | 120 mA | |
| Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin | |
| Bit width in the process image | 8 outputs | |
| Electrical isolation | 500 V | |
| Weight | approx. 165 g | |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable | |
| Approvals | CE, UL, Ex | |
![]() |
![]() |
![]() |